How often, and with which chemical, should a CIP clean be carried out?

The cleaning decision looks not at the calendar but at three measurements: differential pressure, permeate conductivity and production flow. The threshold values, and what to do after a long shutdown.

Diagnose first, then clean

A CIP (cleaning-in-place) wash is not a maintenance routine, it is an intervention. Before cleaning you have to establish what has happened to the membrane; the chemical to be used depends directly on the cause of the fouling.

The wrong chemical not only fails to remove the fouling, it can do permanent damage to the membrane surface.

Thresholds that signal cleaning time

When any one of the values below is observed, cleaning should be carried out without delay.

  • A 10–15% rise in the differential pressure across a membrane stage
  • A 20% rise in permeate conductivity
  • A 10–15% fall in production flow rate

Is it cleaned even when nothing is wrong?

Yes. Even with no symptoms, cleaning every 4–6 months is recommended; if you wait until the build-up shows itself, it becomes harder to remove.

Cleaning is also mandatory after any shutdown longer than 48 hours. In an idle system biological growth on the membrane surface accelerates; on return to production an uncleaned membrane can foul permanently within the first hours.

Choosing the chemical

Acidic cleaning chemicals are used for scale and silica precipitation, alkaline ones for organic and biological fouling. In some cases two stages are needed one after the other.

To make the right choice we look at the system’s historical data and the raw water analysis; a clean carried out on guesswork puts the most expensive consumable at risk.