Water Treatment for Steam Boilers and Power Plants

Treatment lines that control hardness, conductivity and silica in boiler feedwater together, staged by boiler pressure and whether a turbine is present.

In a steam boiler the water evaporates, while the dissolved substances it carries stay behind and concentrate. Hardness forms a scale layer on heat transfer surfaces; this layer raises fuel consumption and causes the tubes to overheat. Dissolved oxygen and carbon dioxide cause corrosion in the boiler and in condensate lines. Blowdown, carried out to keep the concentration of the boiler water within limits, means discarding heated water and chemicals. The quality of the feedwater directly determines all of these losses.

The water quality required varies with the type of boiler and its operating pressure; the limits are set by the boiler manufacturer’s water quality recommendations and the applicable standards. In low-pressure boilers, softening and suitable conditioning are often sufficient. As pressure rises, the limits for conductivity and silica tighten, and in circuits with a turbine silica becomes a heading of its own. At these plants, besides the raw water analysis, we also inspect the condensate return and the existing chemical conditioning on site.

Where water is used

The decisive quality

  • Boiler feedwater

    In the make-up water entering the boiler, the most basic parameter is hardness; any hardness leakage soon turns into a scale layer. As pressure rises, conductivity and silica also become decisive. The lower the dissolved solids content of the feedwater, the less blowdown the boiler needs.

  • Steam turbine cycle

    In circuits with a turbine, steam purity directly affects the efficiency and service life of the turbine. At high pressure, silica is carried with the steam and leaves deposits on the turbine blades that are hard to remove; sodium and conductivity are also monitored continuously on these lines.

  • Condensate return

    Returning condensate is valuable because of the heat it carries and because it is already treated. However, corrosion products, or process material entering through heat exchanger leaks, can be carried into the boiler. Iron and conductivity are decisive; on lines at risk of contamination the condensate is monitored and treated where necessary.

  • Cooling tower and condenser

    The condensers that condense turbine exhaust steam, and auxiliary cooling circuits, often operate with a cooling tower. In tower water concentrated by evaporation, scaling, corrosion and biological growth reduce condenser efficiency; the quality of the make-up water determines the cycles of concentration the tower can reach.

Work out your line in a few steps

The solution finder opens with this sector selected; choose your water source and goal and it shows the treatment stages that fit.

Try the solution finder →

Frequently asked questions

Is water softening enough for a steam boiler?

It depends on the boiler pressure and the salinity of the raw water. In low-pressure boilers, softening together with a deaerator or suitable chemical conditioning is often sufficient. Softening, however, does not lower salinity or silica; with raw water high in dissolved salts the boiler needs frequent blowdown, and reverse osmosis can become economical even at low pressure. As pressure rises, and where a turbine is present, reverse osmosis with a polishing stage is generally required.

Why does silica matter in boiler feedwater?

Silica forms a hard layer on boiler surfaces that conducts heat poorly and is difficult to remove. At high pressure it is carried with the steam and builds up on turbine blades, lowering efficiency. Softening does not remove silica; silica control requires reverse osmosis followed by EDI or by demineralisation with strong base anion resin. Silica is measured as a separate parameter in the raw water analysis.

How can boiler blowdown be reduced?

Blowdown is carried out to keep the concentration of dissolved solids in the boiler water within limits; the purer the feedwater, the less blowdown the boiler needs. Lowering salinity with reverse osmosis and returning clean condensate to the boiler are the two main routes. The savings show up together in water, fuel and conditioning chemicals. We carry out the plant-specific calculation in an efficiency study using operating data.

Send us your raw water analysis and the flow rate you need

Let us size the system together; we will survey the site in person if needed.